AR-054 Window air conditionerExplosion-safe

AR-054 Raam airconditioners voor zone 2The window air conditioner AR-054 is an explosion-safe window-mounted air conditioner designed for use in Zone 2 hazardous areas that must be explosion proof. It provides reliable cooling in areas where gases or vapors may occasionally create an explosive atmosphere.

 The AR-054 is certified under ATEX Directive 2014/34/EU (ATEX114), is CE marked, and designed for use in areas classified as Zone 2.

Request a quote

Common use cases

The window air conditioner AR-054 is commonly used in small enclosures or locations where space is limited.

Marc Moolenaar - Artidor Explosion Safety

Request for information or quotation?

If you need an ATEX-certified window air conditioner for Zone 2 or guidance selecting a compact unit, our team is happy to assist.

Contact us Request a quote

Installation & configuration

The window air conditioner AR-054 fits directly into a window opening and does not require a refrigeration technician. Installation is quick, as the monoblock system is pre-filled with refrigerant.

Energy-efficient operation

The window air conditioner AR-054 uses DC inverter technology, meeting the Ecodesign efficiency standards of European Directive 2009/125/EC.

Compact window integration

 It is the only explosion-safe air conditioner in the Artidor range designed specifically for window mounting, requiring no ceiling, rooftop, or external installation.

Request a quote

Features
  • ATEX certified
  • Complies to the European EdoDesign directive
  • CE marked
  • Explosion-safe for gasses and vapours
  • Suitable for use in Zone 2
  • DC inverter technology
  • Cooling only
  • Very compact, easy installation
  • Environment friendly refrigerant R32
Technical properties
  • Explosion safety:
    II 3 G Ex ec h ic mc IIB+H2 T3 Gc
  • European directives:
    2014/34/EU (ATEX 114), 2014/30/EU (EMC) and 2009/125/EC (EcoDesign)
  • Applied standards:
    EN 14986:2017, EN 60079-0:2018, EN 60079-7:2015 / A1:2018, EN 60079-11:2012, EN 60079-18:2015 / A1:2017, EN 80079-36:2016 and EN 80079-37:2016
  • Certification:
    EU Verklaring van Overeenstemming / Unit Assessment Certificaat
  • Power supply:
    230 V AC
  • Mains frequency:
    50 Hz
  • Electrical connections:
    Fixed cable 3 x 2,5 mm², length 5 meter
  • Ambient temperature:
    -20 °C to +45 °C
  • Operational temperature:
    +18 °C to +43 °C
  • Remote control:
    Infra-red remote control included
  • Refrigerant:
    R32